Home Search Emissions Pollutants About the Database


Motiva Enterprises (1406), Norco

LDEQ Accident Report

Accident #136422
State Police #12-00146
Accident Date2012-01-09
Report Date 2012-01-13
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
BenzeneNo information givenFLARE: HCU flare (EPN-4-84)NONOYESBRQ
ButadieneNo information givenFLARE: HCU flare (EPN-4-84)NONOYESBRQ
Flammable GasNo information givenFLARE: HCU flare (EPN-4-84)NONOYESBRQ
Highly Reactive Volatile Organic Compounds (HRVOCs)No information givenFLARE: HCU flare (EPN-4-84)NONONOBRQ
Hydrogen SulfideNo information givenFLARE: HCU flare (EPN-4-84)NONONOBRQ
#5 Fuel OilNo information givenFLARE: HCU flare (EPN-4-84)NONONOBRQ
GasolineNo information givenFLARE: HCU flare (EPN-4-84)NONOYESBRQ
Lubricating OilNo information givenFLARE: HCU flare (EPN-4-84)NONONOBRQ

Accident Classified As: Below Reportable Quantity (BRQ)

Cause of Problem: Process Upset

The HIC on the low pressure separator (PV-817) was opened to the HCU flare (EPN-4-84) because an atmospheric relief valve (RV-4297) on the rectified absorber column (PV-822) at the Hydrocracking Unit relieved prior to its set point. Hydrocracker Flaring

Discharge Preventable - No Information Given

No Information Given.

Notes/Remedial Actions

RV-4297 was isolated and repaired. Flaring stopped once the unit was stabilized.