Home | Search | Emissions | Pollutants | About the Database |
Accident # | 103619 |
State Police # | 08-01211 |
Accident Date | 2008-03-04 |
Report Date | 2008-03-11 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Volatile Organic Compounds (VOCs) | No information given | API/CPI system sludge sump | NO | NO | YES | 1,333.0 pounds |
Benzene | No information given | API/CPI system sludge sump | NO | NO | YES | 12.0 pounds |
Hydrogen Sulfide | No information given | API/CPI system sludge sump | NO | NO | NO | 1.0 pounds |
Slop Oil | No information given | API/CPI system sludge sump | NO | NO | NO | 420.0 gallons |
Accident Classified As:
gasoline entered the oily water system and caused an upset after operator fails to use appropriate control device
LEL alarms lowered to alert Operations sooner of hydrocarbons in the atmosphere. Process and procedures surrounding mgmt of tank water draws and process indicators will be reviewed. Follow-up letter from DEQ states that C-P failed to notify DEQ within 24 hrs of incident and that the tank operator failed to use a control device to block gasoline from entering wastewater system