Home Search Emissions Pollutants About the Database


Valero (26003), Norco

Releases of Recirculating cooling water

LDEQ Accident Number
Accident Date
Point Source(s) Notes Amount of Release
114193

2009-04-16
Flare No. 1, Flare No. 2
Cause: Refinery cooling water tower CT-405 experienced a valve malfunction which resulted in a loss of cooling water to our Naphtha Hydrotreating unit (NHT). Due to the lack of cooling water, our NHT stripper overhead pressure increased and caused PSV-39-235 to relieve to the flare. Simultaneously when the CT-405 valve malfunction, the recirculating cooling water was released from the basin to the ground and flowed offsite.

Followup: No

Notes:
6,000.0 gallons