Valero (1238), Meraux

LDEQ Accident Report

Accident #102451
State Police #08-00374
Accident Date2008-01-20
Report Date 2008-01-28
Follow-up Date 0000-00-00
Follow-up: No Information Provided

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Sulfur Dioxide1hInstrument Air Compressor - #3 SRU MalfunctionNOYESNOBRQ
Hydrogen Sulfide1hInstrument Air Compressor - #3 SRU MalfunctionNONONO51.0 pounds

Accident Classified As:

Cause of Problem: Instrument Failure

the air register to the Incinerator failed closed, starving the Incinerator of combustion air and resulting in a flameout in the #3 SRU Incinerator. The air register malfunctioned due to ice formation in the instrument. (overnight temperatures in the area were below freezing). The root cause was moisture in the instrument air from an instrument air compressor.

Discharge Preventable - Yes

Notes/Remedial Actions

This incident was preventable because the instrument air line was not run through a drier, and MOUSA has no standard to address this issue. Remedial Measures - MOUSA published a standard that all instrument air from compressors must be run through driers.