Formosa Plastics (288), Baton Rouge

Releases in 2008

LDEQ Accident Number
Accident Date
Point Source/Release CauseNotes
110741

2008-11-11
Point Source(s):
PVC reactor

Pollutant(s):
Vinyl Chloride - 2,036 pounds
Cause of Problem: Human Factors

Operation error caused PVC reactor to release 2036 lb Vinyl Chloride monomer during the rinse/wash cycle subsequent discharge and emptying of the vessel.
No information given
110143

2008-10-16
Point Source(s):
1/2" bleed valve

Pollutant(s):
Ethylene dichloride - BRQ
Cause of Problem: No Information Given

1/2" bleed valve open and potential for reportable quantity to have been exceeded
No information given.
108488

2008-09-01
Point Source(s):


Pollutant(s):
Stormwater - 0
Cause of Problem: Weather

Hurricane Gustav caused stormwater to overflow street curbing and discharge into local drainage, bypassing the facility's permitted stormwater outfalls.
A representative from the facility promised that a written report would be attached to the facility's Monthly Discharge Monitoring Report for September, 2008. Amount of stormwater released is unknown.
107664

2008-07-31
Point Source(s):
NP 110 CND Recovery pump

Pollutant(s):
Ethylene dichloride - BRQ
Hydrochloric Acid - BRQ
Vinyl Chloride - BRQ
Cause of Problem: Piping or Tubing

A patch on a line was leaking slowly. Coming from NP 110 CND recovery pump.
Someone was sent to isolate and patch the release. Amount of ethylene dichloride, hydrochloric acid and vinyl chloride released is unknown. LDEQ report indicates that a written report was received 8/8/08, but that report is not included in LABB's file.
106983

2008-07-03
Point Source(s):
Discharge pump

Pollutant(s):
Vinyl Chloride - 0
Ethylene dichloride - 0
Cause of Problem: Equipment Failure

A pinhole leak developed on a discharge pump, but the cause of the leak was unknown.
The release was stopped by valving out the equipment and ceasing use. Amount of Vinyl Chloride and Ethylene Dichloride released is unknown.
106814

2008-06-27
Point Source(s):
reboiler

Pollutant(s):
Vinyl Chloride - BRQ
Ethylene dichloride - BRQ
Cause of Problem: Equipment Failure

Steam was lost throughout the plant, which caused the reboiler to cool down quickly, which caused the release from a gasket leak on the reboiler.
The release was secured when the steam came back up. Late notification because "they were just tied up." Amount of Vinyl Chloride and Ethylene Dichloride released is unknown. LDEQ report indicates that LDEQ received written report on 7/8/08, but that report is not included in LABB's file.
106331

2008-06-11
Point Source(s):
NT506A tank

Pollutant(s):
Vinyl Chloride - BRQ
Ethylene - BRQ
Hydrochloric Acid - BRQ
Cause of Problem: Equipment Failure

There was a leak on NT506A tank. Readings on the tank were 11 PPM.
Operators pumped the tank down to secure the incident.
105529

2008-05-11
Point Source(s):
Reactor NR301A

Pollutant(s):
Ethylene dichloride - BRQ
Cause of Problem: No Information Given

The reactor NR301A was over-pressured, which caused the relief valve to lift.
No information given.
105531

2008-05-11
Point Source(s):
Quench column NC201C

Pollutant(s):
Ethylene dichloride - BRQ
Vinyl Chloride - BRQ
Hydrochloric Acid - BRQ
Cause of Problem: Piping or Tubing

There was a flange leak on on the transition line to quench column NC201C.
The equipment was shut down, and the pressure was removed. Information later revealed that these were fugitive emissions associated with a permitted source.
105120

2008-04-26
Point Source(s):
Quench filter pump

Pollutant(s):
Vinyl Chloride - BRQ
Ethylene dichloride - BRQ
Hydrochloric Acid - BRQ
Cause of Problem: Equipment Failure

There was a pinhole leak on a quench filter pump.
The leak was isolated, and troubleshooting for repairs was initiated.
104917

2008-04-18
Point Source(s):
tattletale gauge

Pollutant(s):
Vinyl Chloride - BRQ
Cause of Problem: Instrument Failure

Tattletale gage on a relief valve was leaking VCM.
Blocked the relief valve and replaced fittings.
104363

2008-03-29
Point Source(s):
NV-203

Pollutant(s):
Hydrochloric Acid - BRQ
Cause of Problem: Seal or Gasket

Blew a gasket on a HCL gas holder NV-203 due to plant upset from loss of power.
No information given.
104120

2008-03-24
Point Source(s):
column

Pollutant(s):
Ethylene dichloride - BRQ
Cause of Problem: Equipment Failure

Leak from the bottom of a column and EDC leak. The cause of high pressure is unknown. High pressure caused steam to trip and column temperature went down causing expansion which allowed EDC to leak from the seals to the bottom of the column.
Secured.
104122

2008-03-20
Point Source(s):
gaskey into caustic mixer line

Pollutant(s):
Vinyl Chloride - BRQ
Cause of Problem: Seal or Gasket

1" gasket leak into the caustic mixer line. VCM release.
Isolated the line to stop the leak.