Home | Search | Emissions | Pollutants | About the Database |
LDEQ Accident Number Accident Date |
Point Source(s) | Notes | Amount of Release |
114939 2009-05-13 | spent Sulfuric Acid Tank | Cause: An internal chemical reaction occured due to a nitrogen purge being cut off to the tank. The nitrogen purge is utilized for level indication. It is believed that G-1113 reacted with Oxygen to build up in the tank causing an internal chemical reaction leading to the release of HCL, HF, and Oxalic Acid. Followup: No Notes: The area around the tank was barricaded and the #7 mitigation tower was activated as a precautionary measure to reduce the tank temperature. Black smoke was being released from the spent sulfuric acid pump down tank. | 11.5 pounds |