Home | Search | Emissions | Pollutants | About the Database |
LDEQ Accident Number Accident Date |
Point Source(s) | Notes | Amount of Release |
111449 2008-12-15 | MSCCU | Cause: during catalyst removal from MSCCU, a breach of containment resulted in release of catalyst to ground and nearby areas Followup: Yes Notes: Stopped catalyst removal process immediately and clean up the impacted area. Revise catalyst loading and unloading procedure to require gauging of hoppers with a temperature gun or heat scan to allow the level to be tracked with less frequent manual gauging. Set up a log to make sure procedure is followed. | 80.0 pounds |