Home | Search | Emissions | Pollutants | About the Database |
LDEQ Accident Number Accident Date |
Point Source(s) | Notes | Amount of Release |
07-BB011-3196 2007-04-08 | HGU Torvex Incinerator (EPN 79J-904) | Cause: a temp. swing triggered a temperature alarm and an operator responded to the alarm by making adjustments to the operation of the unit Followup: No Notes: Motiva will incorporate control valve set point guidance into supporting documentation for operators to prevent swings in incinerator burner outlet temp. from triggering the low temp. alarm; Implement a troubleshooting guide to assist operators with operating the control valve when it is believed to be sticking. | 176.0 pounds |
102537 2008-01-23 | TORVEX Incinerator EPN 79J-904 | Cause: failure of an antifriction ball bearing in the blower results in shutdown of the incinerator. Followup: No Notes: Rotating equipmt and other supporting engineering personnel will complete the investigation of the failure and implement necessary changes to monitoring inspection and maintenance procedures | 1,203.0 pounds |