Home | Search | Emissions | Pollutants | About the Database |
LDEQ Accident Number Accident Date |
Point Source(s) | Notes | Amount of Release |
76968 2005-02-16 | No. 10 HDS | Cause: Iron sulfide exposure to oxygen. Followup: No Notes: Maintenance procedures will be updated to ensure filter elements remain soaked in water until the maintenance crew is ready to remove them. No excess emissions above reportable quantity, therefore the notification was made as a courtesy. | 45.0 pounds |
112925 2009-02-23 | #1/2 SRU | Cause: A boiler had an emergency shutdown due to a steam imbalance across the site. Various units that depend on steam to operate had rates rapidly reduced, and a release from #1/2 Sulfur Recovery Unit(SRU) was caused. Followup: No Notes: No information given | 69.6 pounds |