Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Sulfur Dioxide0 hr 6 minArea B- South Flare (EP31)NOYESNO 

Accident Classified As:

Cause of Problem: Maintenance/Procedures

The suction pressure on the SFGR compressors dropped below the low-low suction pressure trip point and shutdown the compressor that was running. The suction pressure dropped due to commissioning activites or the South Flare caustic scrubber project.

Discharge Preventable - Yes

Notes/Remedial Actions

Compressor restarted. Troubleshooting performed subsequent to the event reveled that the caustic scrubber level was not sufficient to hold enough backpressure or the recovery compressor suction. The level instrumentation will be revised to prevent reoccurence of this event. HAZMAT #06-01120