Phillips 66 (2538), Lake Charles

LDEQ Accident Report

Accident #77739
State Police #05-01880
Accident Date2005-03-21
Report Date 2005-03-28
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Sulfur Dioxide0hrs 36 mFLARE (South Flare EP-31)NOYESNO420.0 pounds

Accident Classified As:

Cause of Problem: Start Up, Shut Down

SFGR compressors shut down on high flare header pressure. FCC steaming for turnaround elevated flare header pressure (along with 2CTU gas) and when No. 2 Coker went to the blowdown at normal time (not early), it spiked the header pressure up high enough

Discharge Preventable - Yes

Notes/Remedial Actions

Cut FCC steaming back and started SFGR compressors. No excess emissions above permit limits, therefore notification only as courtesy.