Home | Search | Emissions | Pollutants | About the Database |
Accident # | 146671 |
PDF Available | ![]() |
State Police # | 13-00680 |
Accident Date | 2013-02-14 |
Report Date | 2013-02-19 |
Follow-up Date | 0000-00-00 |
Follow-up: |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 1h 49m | Low Pressure Flare | NO | YES | NO | 481.0 pounds |
Accident Classified As: Below Reportable Quantity (BRQ)
Power was inadvertently interrupted to the electronic speed governor for the Fluidized Catalytic Cracking (FCC) Unit's Wet Gas Compressor. The governor performed as designed, reducing the compressor's rotating speed to minimum but not shutting down the machine. The excess gasses the compressor no longer could process were routed to the Low Pressure Flare in order to protect the compressor. The Flare Gas Recovery's Water Seal Drum for the Low Pressure was compromised at the initial onset of this event resulting in flaring.
Operations began the process of increasing the compressor's speed back to normal. Once returned to normal speed and the water seal at the seal drum was re-established, the flaring of all excess gases stopped.
Connect With Us: