Home | Search | Emissions | Pollutants | About the Database |
Accident # | 129163 |
State Police # | 11-00717 |
Accident Date | 2011-02-09 |
Report Date | 2011-02-16 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
1,3-Butadiene | 23h 43m | BELA-5 1,3-Butadiene Unit | NO | NO | YES | 121.0 pounds |
Accident Classified As: Reportable Quantity
Approximately 121 pounds of 1,3-Butadiene was released from the BELA-5 unit after a compressor tripped, causing an unplanned shutdown. The compressor trip was caused by a significant fouling incident on both parallel feed filters. The unit's solvent balance was disrupted when the filters fouled, and the compressor tripped due to a high suction drum level.
Material was routed to the flare per design. The unit was shutdown and multiple filters were cleaned.