Home | Search | Emissions | Pollutants | About the Database |
Accident # | 94692 |
State Police # | 07-01289 |
Accident Date | 2007-03-18 |
Report Date | 2007-03-23 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 0 h 30 m | Gas Recovery Unit - # 1 flare | NO | YES | NO | 1,572.0 pounds |
Accident Classified As:
see notes. #2 coker wet gas compressor and the GRU experienced pressure swings causing the temp. in the comp. to increase and shutdown.
control valve in the GRU was out of calibration. Control valve was sending false signals to the control room indicating that the valve was 100% open. The valve was replaced.