Accident # | 87975 |
State Police # | 06-03123 |
Accident Date | 2006-05-19 |
Report Date | 2006-05-26 |
Follow-up Date | 0000-00-00 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 0 h 50 m | Coker wet gas compressor trip from high level in the interstage drum | NO | YES | NO | 5,600.0 pounds |
Accident Classified As:
Wet gas compressor tripped due to a high level in the suction drum Gas processed by the compressor was directed to the refinery flare system
SO2 released from flares and dispersed. Emissions were minimized by cutting coker charge rates, emptying the liquid level to the interstage drum, and restarting the coker WGC. Flaring of gases stopped upon startup of the coker WGC.