Home | Search | Emissions | Pollutants | About the Database |
Accident # | 105932 |
State Police # | 08-03014 |
Accident Date | 2008-05-25 |
Report Date | 2008-05-30 |
Follow-up Date | 2008-08-29 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Flammable Vapor | 28h | Pressure vacuum vent release | NO | NO | YES | 626.0 pounds |
Accident Classified As: Below Reportable Quantity (BRQ)
Due to excess hydrocarbons in the tanks, the vapor recovery system became overwhelmed and the pressure exceeded the setpoint of the PV vents. Excess hydrocarbons was carryunder from an upstream acid settler drum that had a malfunctioning level instrument.
Hydrocarbon source was blocked from tanks. The reportable quantity for flammable vapor was exceeded.