Honeywell (289, 183605), Baton Rouge

Releases of Chlorodifluoromethane

LDEQ Accident Number
Accident Date
Point Source(s) Notes Amount of Release
101817

2007-12-19
G-22 relief valve
Cause: During operation of the G-22 unit the South Joy compressor was over pressurized causing a relief valve in the inner cooler portion of the machinery to lift. The relief valve failed to reseat properly causing a realase of 3580 lbs of Chlorodifluoromethane (G-22).

Followup: No

Notes:
3,580.0 pounds
122636

2010-04-08
pressure transmitter
Cause: The plant was in the process of repairing a pressure transmitter. When the transmitter was isolated for repair, this inadvertently caused an over pressure of the system.

Followup: No

Notes: DUring the over pressure, the relief valves on the system opened as designed. The relief valves vented through the low pressure scrubber system and then to the air.
651.0 pounds