Home | Search | Emissions | Pollutants | About the Database |
LDEQ Accident Number Accident Date |
Point Source(s) | Notes | Amount of Release |
No LDEQ Reported 2007-12-21 | HGU WWTU Flare EPN 85D-105 | Cause: see notes. Flame outage on flare causes release. Followup: No Notes: Under investigation - no remedial actions specified | |
99010 2007-08-28 | HGU WWTU Flare EPN 85D-105 | Cause: upset of natural gas flow to the flare results in a pilot outage Followup: No Notes: Under investigation - no remedial actions specified | |
102246 2008-01-12 | HGU WWTU Flare (EPN 85D-105) | Cause: malfunctioning level controller let to Pilot outage on flare due to liquid extinguishing the flare. Followup: No Notes: Cold weather led to salt disposition on a level gauge that suppressed the high level alarm on the flare knock out drum. Letter states that remedial action will be taken, but does not specify whic | |
08-BB011-3258 2008-01-05 | HGU WWTU Flare (EPN 85D-105) | Cause: see notes. Pilot outage on flare Followup: No Notes: Under investigation. Affirmative defense letter. | >RQ |
113955 2009-04-04 | SRU-4 thermal reactor; TGTU-3 | Cause: Level 2 fire at Sulfur Recovery Unit (SRU)no. 4's thermal reactor due to failure of the SRU-4 thermal reactor vessel. Tail Gas Treating Unit (TGTU) No. 3 upset during firefighting efforts causing additional emissions.
Fenceline monitoring indicated no offsite impacts.
Exceeded RQs. Followup: Yes Notes: In-house fire dept and ERT worked to extinguish fire, reduced operating rates on units producing acid gas or rich amine and to distribute the acid gas flow to other operation SRU/TGTUs during firefight to safely shut down SRU/TGTU-4. | 2.0 pounds |
155952 2014-05-12 | LUI West Tank Farm, Tank 20D-2 | Cause: Waste water containing ammonia salts and phosphoric acid leaked through a roll-off box and a secondary-containment unit that had a small hole. The box and the collapsible secondary-containment unit were themselves inside an earthen containment.
Both the primary and secondary containment systems failed in this case. The incident occurred at the LUI West Tank Farm, Tank 20D-2. Followup: No Notes: Letter did not indicate that any remediation activities had occurred, nor that the containment units had been replaced or repaired. |
Connect With Us: