No LDEQ Reported 2008-05-17 | FLARE-PSV-84 relief valve on Reactor (491-V-49) | Cause: Valve failure cause by a power surge from lightening. Followup: Yes Notes: Incident due to a valve failure caused by a power surge from lightning. Motor control and trim on valve fixed. | 8.0 pounds |
136882 2012-02-01 | 1391-FF (1391-PSV-009) | Cause: There was an unexpected increase in the Depantanizer tower's overhead pressure causing PSV-009 to relieve. This was the result of the shutdown of the reboiler due to high burner pressure. Followup: No Notes: The reboiler (1391-H-4) temperature was lowered which lowered the pressure in the Depantanizer Tower allowing 1391-PSV-009 to reseat. There is no LDEQ report and no SPOC report attached to this file. 19,570 pounds released | 3.3 |