93398 2007-01-22 | Tank Farm | Cause: Unknown Followup: No Notes: Inspected floating roof seals, cleaned the area with vacuum truc | 10,500.0 gallons |
106519` 2008-06-17 | Tank 32 | Cause: Tank overfilled Followup: No Notes: Vacuum truck and removal of the contaminated soil | 420.0 gallons |
119349 2009-11-08 | tank farm | Cause: Approximately 700 barrels of naphtha were discharged from the roof of tank 58. The gauging system had failed and manual readings were not taken. Followup: Yes Notes: Stopped flow into tank, foamed product,removed naphtha from within diked area. | 29,400.0 gallons |
156145 2014-05-23 | Platform Unit Charge Heater #1 (EQT 250) | Cause: Rupture of tube in heater fire box. No 1 Platformer charge heater (EQT 0250) exceeded opacity >20% for approximately 20 minutes. The unit was turned off and cooled. Followup: No Notes: Feed and fuel into heater were removed, steamed out and water was sprayed to cool. The report states that the heater tubes will be repaired to proven recurrence. A field interview was conducted on 5/23 and photos were taken which are included in the pdf file. At the time of the inspection, a steam plum exhaust from the heater stack due to water sprayed on to the heater to cool the unit. | No information Given |