Home | Search | Emissions | Pollutants | About the Database |
Accident # | 78898 |
State Police # | 05-03019 |
Accident Date | 2005-05-07 |
Report Date | 2005-05-11 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 9hrs 10m | FLARE (South Flare EP-31) | NO | YES | NO | 8,400.0 pounds |
Accident Classified As:
Failure of O2 Analyzer; failed and tripped out the South flare gas recovery system.
Instrument craftsmen is repairing the analyzer. Previously identified capital project w/in days of completion installs 2 redundant, non-intrusive 02 analyzers with 2 of 2 voting required for shutdown.