Home | Search | Emissions | Pollutants | About the Database |
Accident # | 107212 |
State Police # | 08-04248 |
Accident Date | 2008-07-15 |
Report Date | 2008-07-22 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Hydrogen Sulfide | 0 h 5 m | Sulften Vent EQT297 ; Tail Gas II Stack EQT 298 | NO | NO | NO | 133.0 pounds |
Benzene | 0 h 5 m | Sulften Vent EQT297 ; Tail Gas II Stack EQT 298 | NO | NO | YES | 93.0 pounds |
Sulfur Dioxide | 0 h 5 m | Sulften Vent EQT297 ; Tail Gas II Stack EQT 298 | NO | YES | NO | 1,000.0 pounds |
Accident Classified As:
Some pollutants released onto Highway, which was sealed off during clean up. 5.5 inches of rain in a 3 hour period led to depressurization in process units and various instrumentation problems; event met or approached the 25-year 3-hour intensity standard; Install three additional sumps, pumps, and associated piping in the steam trench to alleviate flooding during heavy ra