Home | Search | Emissions | Pollutants | About the Database |
Accident # | 77549 |
State Police # | 05-01699 |
Accident Date | 2005-03-13 |
Report Date | 2005-03-18 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Carbon Monoxide | 35m | C-2307 (Second Stage High-Pressure Separator) level controller; K-2303 (HCU Second Stage Recycle Compressor) | NO | YES | NO | 176.0 pounds |
Hydrocarbon | 35m | C-2307 (Second Stage High-Pressure Separator) level controller; K-2303 (HCU Second Stage Recycle Compressor) | NO | NO | YES | 68.0 pounds |
Hydrogen Sulfide | 35m | C-2307 (Second Stage High-Pressure Separator) level controller; K-2303 (HCU Second Stage Recycle Compressor) | NO | NO | NO | |
Nitric Oxide | 35m | C-2307 (Second Stage High-Pressure Separator) level controller; K-2303 (HCU Second Stage Recycle Compressor) | NO | YES | NO | 29.0 pounds |
Nitrogen Dioxide | 35m | C-2307 (Second Stage High-Pressure Separator) level controller; K-2303 (HCU Second Stage Recycle Compressor) | NO | YES | YES | 3.0 pounds |
Sulfur Dioxide | 35m | C-2307 (Second Stage High-Pressure Separator) level controller; K-2303 (HCU Second Stage Recycle Compressor) | NO | YES | NO | 12.0 pounds |
Accident Classified As: Below Reportable Quantity (BRQ)
During maintenance, the Hydrocracker (HCU) Second Stage High-Pressure Separator (C-2307) level controller was inadvertently left in the manual position. Later, HCU Second Stage Recycle Compressor (K-2303) shut down due to high level in C-2307. Shutdown of K-2303 caused automatic depressurization of C-2307 to the refinery flare system.
Letter rescinds report of Sulfur Dioxide because below reportable quantity.
Connect With Us: