Home Search Emissions Pollutants About the Database


CITGO Petroleum (1250), Lake Charles

LDEQ Accident Report

Accident #98539
State Police #07-04578
Accident Date2007-08-09
Report Date 2007-08-13
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
AmmoniaNo information givenCooling Tower 1 and 2NONONO195.0 pounds

Accident Classified As:

Cause of Problem: Corrosion

of heat exchanger tubing that releases ammonia into the hot water that goes to the cooling tower

Discharge Preventable - No

Notes/Remedial Actions

Leak occurred at York Ammonica System C-52A Condenser at C-4 Recovery Unit. Leaking tubes plugged and all tubes in heat exchanger are Seakaphen coated to resist corrosion. EXTREMELY HAZARDOUS.