Home Search Emissions Pollutants About the Database


ExxonMobil Refinery (2638), Baton Rouge

LDEQ Accident Report

Accident #157225
State Police #14-02955
Accident Date2014-07-04
Report Date 2014-07-09
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Sulfur Dioxide56mGLA-1X Compressor at PCLA unitNOYESNO2,611.0 pounds

Accident Classified As: Reportable Quantity

Cause of Problem: Instrument Failure

On 7/4/2014 the GLA-1X compressor at the PCLA unit experiences an unplanned shut down, causing material to be released to the site's flare gas system. As a result of water entering a flow meter, the meter reading incorrectly held constant while the flow increased. This led to a rapid increase in the compressor distillate drum level and when the emergency high level was reached, the protective system tripped the compressor, leading the the flaring of sulfur dioxide.

Discharge Preventable - No Information Given

Reported as undetermined, no indication that there is an investigation.

Notes/Remedial Actions

Immediately upon compressor shut down, the flow meter was repaired and the compressor was restarted. Further actions to prevent recurrence are the implementation of an alarm notification to notify operations team of flow rate deviations and valve position.