Home | Search | Emissions | Pollutants | About the Database |
Accident # | 76595 |
State Police # | 05-00704 |
Accident Date | 2005-01-30 |
Report Date | 2005-02-04 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Nitric Oxide | 2h 10m | Pressure Safety Valve (PSV) on the Hydrocracker Light Ends Plant (LEP) A stripper as the source of the increased flame at number 2 flare | NO | YES | NO | 15.0 pounds |
Sulfur Dioxide | 2h 10m | NO | YES | NO | 1.0 |
Accident Classified As: Reportable Quantity
An abrupt increase in light material to the LEP A Stripper exceeded the tower overhead condenser cooling capacity, causing tower to overpressure.
After identifying the LEP A Stripper PSV flaring, cooling water in the A Stripper overhead was increased which condensed additional light materials in the tower; this lowered the pressure on the tower to end the incident.