Accident # | 147803 |
State Police # | 13-01409 |
Accident Date | 2013-04-03 |
Report Date | 2013-06-07 |
Follow-up Date | 0000-00-00 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 10h 22m | Coker 2 Gas Compressor | NO | YES | NO | 24,480.0 pounds |
Accident Classified As: Reportable Quantity
A lightning strike caused a temporary loss of power from Entergy resulting in a shutdown of the K8101 wet gas compressor. On Wednesday, April 3, 2013, at approximately 1026 hours, Chalmette Refinery experienced a disruption in power service causing the coker 2 gas compressor to trip (K8101). This resulted in the fractionator overhead valve opening to the flare system to control the pressure. K8101 restart attempts failed and the flare gas management (FGM) compressors stopped pumping from the increased molecular weight. Flare 1 was out of service for maintenance activities and the gas was routed to the #2 Flare system to ensure safe operations. K8101 was restarted at 1420 hours and at approximately 1640 hours the FGM compressors were restarted and H2S levels decreased. All systems were normal at 1800 hours.
CRLLC could not have anticipated a disruption in power from a third party.
After several attempts to restart K8101 flare gasses were routed to the #2 Flare to ensure safe operations. All efforts were taken to get the flare system back in normal operation as quickly as possible.