ExxonMobil Chemical Plant (286), Baton Rouge

LDEQ Accident Report

Accident #147280
State Police #13-24560
Accident Date2012-11-17
Report Date 2013-01-18
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
AmmoniaNIGammonia scrubber water control valveNONONO619.1 pounds

Accident Classified As: Below Reportable Quantity (BRQ)

Cause of Problem: Human Factors

The Baton Rouge Chemical Plant is permitted under permit number 2390-V2 to unload ammonia railcars. The resulting ammonia emissions are routed through an ammonia water scrubber before emitting from vent stack V-462. On November 17, 2012, the ammonia scrubber water control valve was inadvertently placed in manual control. The valve remained closed until discovery on January 11, 2013.

Discharge Preventable - No Information Given

Notes/Remedial Actions

Additional training, alarm management, and stewardship will be instituted to prevent recurrence.