Home Search Emissions Pollutants About the Database


Valero (1238), Meraux

LDEQ Accident Report

Accident #141027
tate Police #N/A
Accident Date2012-07-07
Report Date 2012-08-03
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
HydrocarbonNo Information GivenNorth FlareNONOYESBRQ

Accident Classified As: Below Reportable Quantity (BRQ)

Cause of Problem: No Information Given

The flow of chilled water to the C3/C4 Splitter's overhead condensers unexpectedly decreased, causing a pressure increase within the tower. To relieve the pressure, splitter overhead material was relieved to the North Flare.

Discharge Preventable - No Information Given

Notes/Remedial Actions

A citizen complaint on 7/7/12 described in the morning, the north flare had a very low flame with a black trail. In the pm, there was a high jet burn then low jet burn with black trail light. There was also an odor in the air. A surveillance conducted on 7/16 and 7/20 of the area found no large flare or black trails observed. An odor was not detected at the time of the inspections. To minimize the flaring, the FCC charge rate was reduced. The chilled water heat exchangers were backflushed. This, combined with increasing the chilled water circulation rate, reduced the pressure in the tower and stopped the flaring. While the release to the North Flare caused a temporary exceedence of Title V and Consent Decree limits, no CERCLA/EPCRA reportable quantities were released. No reportable quantities were released during the subsequent flaring to relieve pressure within the tower. Claims they will submit the appropriate periodic reports regarding the exceedences, but no such report attached.