Home | Search | Emissions | Pollutants | About the Database |
Accident # | 77932 |
State Police # | 05-02123 |
Accident Date | 2005-04-01 |
Report Date | 2005-04-07 |
Follow-up Date | 2005-04-11 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
chlorotrifluoroethylene | 10m | NO | NO | NO | 837.0 pounds |
Accident Classified As: Reportable Quantity
While loading chlorotrifluoroethylene (G-1113) from a storage tank to a ton cylinder, the release occured to the process sump via stack drain line due to improper valve alignment.
The valve on the storage tank was closed to stop any flow of chlorotrifluoroethylene (G-113) to the cylinder. Plant personnel were evacuated until determination was made by the emergency response team that the area around the release was safe. As a result of this incident, Honeywell reviewed computer data for trends, operating procedures, training, opened up several lines for possible pluggage, replaced several remote operated valves to prevent any leakage, etc.
Connect With Us: