Home | Search | Emissions | Pollutants | About the Database |
Accident # | 115845 |
State Police # | No Information Given |
Accident Date | 2009-06-20 |
Report Date | 2010-03-25 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Propylene | No Information Given | WCT 01 | NO | NO | YES | 171.0 pounds |
Accident Classified As: No Information Given
Safety valve on WCT 01 failed and released to flare. Root cause for flaring was positional failure of the control valve resulting in a pressure surge to the tower WCT01. The safety valve did not properly seal after the lift and VOCs leaked to the flare.
Uncombusted propylene released through the flare.
Connect With Us: