Home | Search | Emissions | Pollutants | About the Database |
Accident # | 109029 |
PDF Available | ![]() |
State Police # | 08 - 05850 |
Accident Date | 2008-09-13 |
Report Date | 2008-09-13 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 15 H | FL 2001 #3 Flare | NO | YES | NO | 12,800.0 pounds |
Hydrogen Sulfide | vacuum truck loading area, flare line knock-out drum | NO | NO | NO | BRQ |
Accident Classified As: Reportable Quantity
Hurricane Ike blew down 2 power poles inside the refinery causing plant power failure. Both Sulfur Recovery Units (SRUs) were down and all acid gas was routed to the #3 flare. The boilers were also down and there was no steam on the flare. As a result the #3 flare opacity was greater than 20% for 2 hours. While in start-up, refinery operators noted that the flare pressure was higher than normal. The investigation revealed that the flare knock-out drums were full of liquid and the flare lines had liquid in them as well.
Hurricane Ike winds blew down two power poles inside the refinery.
Power lines and poles were replaced In response to problems during start-up, contractors were immediately brought in to provide vacuum truck services, and the liquids removed from the knockout drums and flare lines was placed into Baker fractionation tanks. The Vacuum truck operations of removing the liquid from the flare line had the unfortunate result of creating odor problems within the refinery. Low levels of Hydrogen Sulfide were detected around the vacuum truck loading areas and at the three flare line knock-out drums. Calumet personnel monitored hydrogen sulfide levels within the refinery for industrial hygiene purposes. Liquids from the Sour Water Stripper were also found to be entering the flare lines, adn the sources of these liquids were identified and blinded off.
Connect With Us: