Motiva Enterprises (1406), Norco

LDEQ Accident Report

Accident #124186
tate Police #N/A
Accident Date2010-06-15
Report Date 2010-06-22
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Benzene9h 20mWharf Berth 1: high sulfur light product lineNONOYES59.0 pounds
Xylene9h 20mWharf Berth 1: high sulfur light product lineNONONO162.0 pounds
Naptha (Crude)9h 20mWharf Berth 1: high sulfur light product lineNONOYES280.0 gallons
Hexane9h 20mWharf Berth 1: high sulfur light product lineNONONO115.0 pounds
Ethylbenzene9h 20mWharf Berth 1: high sulfur light product lineNONOYES28.0 pounds
m-Xylene9h 20mWharf Berth 1: high sulfur light product lineNONONO162.0 pounds
Toluene9h 20mWharf Berth 1: high sulfur light product lineNONONO95.0 pounds
2,3,3-Trimethylpentane9h 20mWharf Berth 1: high sulfur light product lineNONOYES87.0 pounds
1,2,4-Trimethylbenzene9h 20mWharf Berth 1: high sulfur light product lineNONOYES49.0 pounds
Styrene9h 20mWharf Berth 1: high sulfur light product lineNONONO9.0 pounds
1,3-Butadiene9h 20mWharf Berth 1: high sulfur light product lineNONOYES0.0 pounds
Butane9h 20mWharf Berth 1: high sulfur light product lineNONOYES39.0 pounds
Cresol9h 20mWharf Berth 1: high sulfur light product lineNONOYES0.0 pounds
Cumene9h 20mWharf Berth 1: high sulfur light product lineNONOYES3.0 pounds
Unknown Substance9h 20mWharf Berth 1: high sulfur light product lineNONONO1,089.0 pounds
Naphthalene9h 20mWharf Berth 1: high sulfur light product lineNONOYES11.0 pounds

Accident Classified As:

Cause of Problem: Corrosion

LDEQ report states, "Motiva reported a leaking high sulfur light product line at the wharf that released approximately six barrels of naptha to the Mississippi River. Leak was caused by external corrosion, and two contributing factors were identified. First, the line was found to be in contact with the insulation of adjacent piping, causing water accumulation between the lines. Additionally, inadequate coating was discovered on the blistered section of piping." A total of 1,748 pounds of chemicals were released to the air.

Discharge Preventable - Yes

"This release has been classified as preventable."

Notes/Remedial Actions

RQ. LDEQ report states that "Motiva took the following measures to prevent reoccurrence of this incident: the blistered section of piping will be replaced so it does not contact near-by equipment and the new line will be adequately coated to protect from external corrosion. Motiva has determined that the release was preventable. This incident is an area of concern with regards to LAC 33:III.905 and LAC 33:IX.501.D."