Home Search Emissions Pollutants About the Database


Motiva Enterprises (2719), Convent

LDEQ Accident Report

Accident #87435
State Police #06-1188
Accident Date2006-04-26
Report Date 2006-05-03
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Aviation Fuelno information givenno information givenNONOYES714.0 gallons

Accident Classified As:

Cause of Problem: Weather

Leaking avjet (aviation jet fuel) filters were replaced due to a leak, old ones placed in a dumpster with an open top, new ones not used until the next day. Dumpster overfilled and leaked during heavy rain; new filters leaked avjet into a catch basin and sprayed into shell area. One bbl spilled to shelled area, one bbl to nearby ditch, 15 bbls to a catch basin.

Discharge Preventable - Yes

Notes/Remedial Actions

Vacuum truck used to clean up spill to ditch and catch basin, contaminated soil removed. "The dumpster will have a lid in the future and taken to appropriate waste slab after the job is complete. Personnel will be instructed on the proper installation of "O" ring around the lid of the canister.