Home Search Emissions Pollutants About the Database


Phillips 66 (2418), Belle Chasse

LDEQ Accident Report

Accident #80112
State Police #05-04249
Accident Date2005-06-26
Report Date 2005-07-01
Follow-up Date 2000-00-00
Follow-up: Yes

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Butane0h 5mSaturate Gas Unit (7991-PSV-18)NONOYES91.0 pounds
Hydrogen Sulfide0h 5mSaturate Gas Unit (7991-PSV-18)NONONO90.0 pounds
Propane0h 5mSaturate Gas Unit (7991-PSV-18)NONOYES8,881.0 pounds

Accident Classified As:

Cause of Problem: Instrument Failure

Pressure control valve BPC-244 malfunctioned gave a false signal of being open when actually in the closed position. This caused the pressure relief valve 7991-PSV-18 to lift for 5 minutes.

Discharge Preventable - No

The false valve position hindered the response to know something was wrong.

Notes/Remedial Actions

Assured they would operate this at a Òlow pressureÓ pending findings of the investigation.