Accident # | 80112 |
State Police # | 05-04249 |
Accident Date | 2005-06-26 |
Report Date | 2005-07-01 |
Follow-up Date | 2000-00-00 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Butane | 0h 5m | Saturate Gas Unit (7991-PSV-18) | NO | NO | YES | 91.0 pounds |
Hydrogen Sulfide | 0h 5m | Saturate Gas Unit (7991-PSV-18) | NO | NO | NO | 90.0 pounds |
Propane | 0h 5m | Saturate Gas Unit (7991-PSV-18) | NO | NO | YES | 8,881.0 pounds |
Accident Classified As:
Pressure control valve BPC-244 malfunctioned gave a false signal of being open when actually in the closed position. This caused the pressure relief valve 7991-PSV-18 to lift for 5 minutes.
The false valve position hindered the response to know something was wrong.
Assured they would operate this at a Òlow pressureÓ pending findings of the investigation.