Home Search Emissions Pollutants About the Database


Phillips 66 (2418), Belle Chasse

LDEQ Accident Report

Accident #91249
State Police #06-06337
Accident Date2006-10-10
Report Date 2006-10-16
Follow-up Date 2000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Hydrocarbon6h 18m308F-D-1 Low Pressure FlareNONOYES904.8 pounds

Accident Classified As:

Cause of Problem: Process Upset

The water boot control valvve for the straight run debutanizer malfunctioned and at the same time the water boot level indicator malfunctioned and began transmitting false levels

Discharge Preventable -

Notes/Remedial Actions

Stabilized using the manual by-pass and a replacement control valve was ordered and hot shot shipped to the refinery. The replacement control valve was installed that same evening. The level indicator was checked, cleaned and placed back in service.