Home Search Emissions Pollutants About the Database


Chalmette Refining (1376), Chalmette

LDEQ Accident Report

Accident #99496
State Police #07-05554
Accident Date2007-09-16
Report Date 2007-09-21
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Hydrogen Sulfide1 h 19 mCat Feed Hydrotreater UnitNONONO2,334.0 pounds
Volatile Organic Compounds (VOCs)1 h 19 mCat Feed Hydrotreater UnitNONOYES24,066.0 pounds

Accident Classified As:

Cause of Problem: Corrosion

piping failure due to corrosion from leak of DGA and H2S into piping system from DGA contactor. Drop in reactor pressure on the CFHT unit. Leak on outlet piping of the Fin Fan. Emer. shutdown due internal corrosion from a leak of diglycolame/Hydrogen Sulfide

Discharge Preventable - Yes

Notes/Remedial Actions

Emergency shutdown was initiated. Water spray was applied to decrease emissions until the unit could be safely depressured. CRLLC inspected entire piping system and ID' other corroded areas. CRLLC plans to increase frequency of outlet piping system inspections. DEQ letter of 10/11/07 indicates that incident will be referred to enforcement because it is preventable.