Home | Search | Emissions | Pollutants | About the Database |
Accident # | 96791 |
State Police # | 07-1865 |
Accident Date | 2007-06-05 |
Report Date | 2007-06-11 |
Follow-up Date | 2007-11-06 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Volatile Organic Compounds (VOCs) | 26h 40m | HCU flare | NO | NO | YES | 495.8 pounds |
Hydrogen Sulfide | 26h 40m | HCU flare | NO | NO | NO | 49.8 pounds |
Flammable Gas | 26h 40m | HCU flare | NO | NO | YES | 3,671.6 pounds |
Accident Classified As: Reportable Quantity
Control valve 755 malfunctioned, sending hydrogen sulfide gas to flare.
Operations closed instrument air supply line, causing valve to go into fail-safe open position. Faulty instrument air filter was repaired and re-established instrument airflow to valve. To prevent recurrence, instrument air supply filter and parts of controller were replaced.