Home | Search | Emissions | Pollutants | About the Database |
Accident # | 115990 |
State Police # | 091967 |
Accident Date | 2009-06-25 |
Report Date | 2009-07-02 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 1h 17m | West Flare | NO | YES | NO | 1,707.0 pounds |
Accident Classified As:
Wet gas compressor tripped on low lube oil pressure. Report makes note that lube oil pressure should be verified by operators prior to switching pumps to prevent unit shutdown.
Lube oil pressure should be verified by operators prior to switching pumps to prevent unit shutdown.
Modify anti-surge controller pressure transmitter set-points to allow restart or alert operation that pressure is reading top of scale.