Accident # | 115395 |
State Police # | 091702 |
Accident Date | 2009-07-02 |
Report Date | 2009-07-31 |
Follow-up Date | 2009-10-02 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 39 minutes | Flares 1, Flare 2 | NO | YES | NO | 4,241.5 pounds |
Carbon Monoxide | 39 minutes | Flares 1, Flare 2 | NO | YES | NO | 106.9 pounds |
Nitrogen Dioxide | 39 minutes | Flares 1, Flare 2 | NO | YES | YES | 19.6 pounds |
Volatile Organic Compounds (VOCs) | 39 minutes | Flares 1, Flare 2 | NO | NO | YES | 40.4 pounds |
Hydrogen Sulfide | 39 minutes | Flares 1, Flare 2 | NO | NO | NO | 11.3 pounds |
Particulate Matter | 39 minutes | Flares 1, Flare 2 | NO | YES | NO | 0.8 pounds |
Accident Classified As:
While performing a preventative maintenance check. While checking voltage output levels on the power supplies in the control cabinets an arc was created that shut down both power supply #1 an #2. The loss of both power supplies caused the redundant controllers to power down, which shutdown the Coker Wet Gas Compressor sending material to the flare.
incident is believed to have been reasonably preventable
Wet gas compressor was immediately restarted