Home Search Emissions Pollutants About the Database


Phillips 66 (2418), Belle Chasse

LDEQ Accident Report

Accident #116329
State Police #09-03612
Accident Date2009-07-09
Report Date 2009-07-16
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Methane/Ethane Mixture15 minutes410-PSV-061NONOYES12,284.0 pounds

Accident Classified As:

Cause of Problem: Process Upset

Pressure in the refinery instrument air supply system decreased unexpectedly which resulted in the loss of pressure control at the Enbridge purchased fuel gas control station (on the property of the refinery). This loss of pressure control caused the PSV (410-PSV-061) to lift until proper pressure within the instrument air system could be restored.

Discharge Preventable - No

Unexpected decrease of refinery instrument air pressure caused a PSV to lift until the proper air pressure could be restored.

Notes/Remedial Actions

Immediately regained control of the plant fuel gas system manually. "No offsite impact was noted."