Home | Search | Emissions | Pollutants | About the Database |
Accident # | 111957 |
State Police # | 09-00170 |
Accident Date | 2008-01-11 |
Report Date | 2009-01-16 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | No Information Given | flare and PCLA F-301/F-201 furnace | NO | YES | NO | 633.0 pounds |
Accident Classified As:
Emergency isolation valve on GLA-2X compressor failed to close. This caused pressure build up in PCLA system, in which the control valve routed the excess gas to the flare system.
Motor on an emergency isolation valve malfunctioned, causing the control valve to close unexpectedly.
Under investigation. Exceeded RQ due to the combination from the flare and the PCLA F-301/F-201 furnace leaks (LSP Incident #08-07087).