Home Search Emissions Pollutants About the Database


Valero (26003), Norco

LDEQ Accident Report

Accident #76407
State Police #05-00533, 05-00545
Accident Date2005-01-24
Report Date 0000-00-00
Follow-up Date 0000-00-00
Follow-up: Yes

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Sulfur Dioxide10 h 0 mCoker wet gas compressorNOYESNO23,000.0 pounds

Accident Classified As:

Cause of Problem: Instrument Failure

The WGC tripped several times due to a high level indication in the interstage drum. This indication was a fase reading due to an accumulation of debris in the level chamber of the radar detector.

Discharge Preventable - Yes

Notes/Remedial Actions

Will place the level chamber on a cleaning schedule to facilitate the removal of debris no later than April 15, 2005.