Home | Search | Emissions | Pollutants | About the Database |
Accident # | 76407 |
State Police # | 05-00533, 05-00545 |
Accident Date | 2005-01-24 |
Report Date | 0000-00-00 |
Follow-up Date | 0000-00-00 |
Follow-up: | Yes |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 10 h 0 m | Coker wet gas compressor | NO | YES | NO | 23,000.0 pounds |
Accident Classified As:
The WGC tripped several times due to a high level indication in the interstage drum. This indication was a fase reading due to an accumulation of debris in the level chamber of the radar detector.
Will place the level chamber on a cleaning schedule to facilitate the removal of debris no later than April 15, 2005.