Home | Search | Emissions | Pollutants | About the Database |
Accident # | 97825 |
State Police # | 06-03900 |
Accident Date | 2007-07-12 |
Report Date | 2007-07-20 |
Follow-up Date | 0000-00-00 |
Follow-up: | No Information Provided |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 1h | Thermal Reactor | NO | YES | NO | 113.0 pounds |
Accident Classified As:
MOUSA shut down the #2 SRU in order to inspect a visible leak in the Thermal Reactor. MOUSA found localized corrosion damage to the shell resulting from acid gas infiltrating a small defect in the refractory.
This incident was not preventable because the leak in the Thermal Reactor was not a predictable event. Remedial Measures - MOUSA shut down the unit, conducted a thorough inspection, and patched the leak in accordance with API 510. MOUSA will repair the internal refractory during the next scheduled turnaround. MOUSA conducts routine on-stream ultrasonic inspections on this unit to monitor equipment fitness