Home Search Emissions Pollutants About the Database


Motiva Enterprises (1406), Norco

LDEQ Accident Report

Accident #107061
State Police #08-04071
Accident Date2008-07-09
Report Date 2008-07-14
Follow-up Date 2008-08-04
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Hydrogen Sulfide0 h 2 mHydrocracker Unit Rectifier Absorber Column (PV-822)NONONO0.8 pounds
Flammable Gas0 h 2 mHydrocracker Unit Rectifier Absorber Column (PV-822)NONOYES63.0 pounds
Volatile Organic Compounds (VOCs)0 h 2 mHydrocracker Unit Rectifier Absorber Column (PV-822)NONOYES24.7 pounds

Accident Classified As: Below Reportable Quantity (BRQ)

Cause of Problem: Equipment Failure

A pressure swing at the HCU caused relief valve on the HCU Rectifier Absorber column (PV-822) to open to atmosphere. HCU was in process of being started post-turnaround.

Discharge Preventable - Yes

Notes/Remedial Actions

Motiva has modified a low level alarm on the HCU High Pressure Separator to mitigate the pressure swings on the Rectifier Absorber Column.