Home | Search | Emissions | Pollutants | About the Database |
Accident # | 81353 |
State Police # | 05-2849 |
Accident Date | 2005-08-16 |
Report Date | 2005-08-18 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sanitary Sewage | No information given | Sanitary sewer lift station | NO | NO | NO | 50.0 gallons |
Sanitary Sewage | No information given | Wastewater treatment facility, LPDES Outfall 06 | NO | NO | NO | BRQ |
Accident Classified As: No Information Given
A portion of the treatment process for the released material was bypassed -- traced to maintenance work performed on 08/11/05 to install a conduit seal on the lift station; the lift station was incorrectly re-wired after the installation, which disabled the automatic start function of the lift station pump.
Control switch on sanitary lift station pump was switched from automatic to manual position, starting the pump and stopping overflow. A vacuum truck was used to removed the liquid from the lift station and prevent additional overflow. While a portion of the process was bypassed, Motiva noted that the material did receive treatment prior to discharg