Accident # | 86878 |
State Police # | 06-01967 |
Accident Date | 2006-03-31 |
Report Date | 2006-04-07 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Sulfur Dioxide | 0 h 26 m | Emergency Flare System AE-AOA-05-0109 EPN 29 | NO | YES | NO | 3,174.0 pounds |
Accident Classified As:
waste gas compressors 4 and 3 (K406 and 402) automatically shut down, lowering the refinery capacity and causing overpressure to the emergency flare system. Liquid level pump (G476) switch was in the off position.
A mechanical guard was placed on the pump switch in order to avoid the unintentional movement of the switch