Home Search Emissions Pollutants About the Database


ExxonMobil Refinery (2638), Baton Rouge

LDEQ Accident Report

Accident #89635
State Police #06-04774
Accident Date2006-08-01
Report Date 2006-08-04
Follow-up Date 0000-00-00
Follow-up: No

Pollutants Released

Pollutant Duration Point Source Greenhouse Gas Criteria Pollutant Ozone forming chemical Amount of Release
Hydrogen Sulfide8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO32.0 pounds
Volatile Organic Compounds (VOCs)8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONOYES6,955.0 pounds
Xylene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO847.0 pounds
Pseudocumene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO681.0 pounds
Toluene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO411.0 pounds
o-Xylene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO311.0 pounds
Ethylbenzene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONOYES151.0 pounds
Naphthalene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONOYES116.0 pounds
Benzene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONOYES42.0 pounds
n-Hexane8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO25.0 pounds
Cyclohexane8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONOYES17.0 pounds
Cumene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONOYES6.0 pounds
Phenol8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO1.0 pounds
Styrene8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO2.0 pounds
Quinoline8h 50 minE-205 C/D exchanger bank on the Heavy Cat Naptha UnitNONONO1.0 pounds

Accident Classified As:

Cause of Problem: Corrosion

the E-205 C/D exchanger bank on the Heavy Cat Naptha unit was leaking to Cooling Tower #27. The leak is believed to be from corrosion on the tube bundle.

Discharge Preventable - No

Notes/Remedial Actions

This incident was not preventable because the inspection data for this bank of exchangers did not indicate that a failure was imminent. These bundles were tested in January 2005 and were found to have no leaks. Remedial Measures - the exchanger bundle will be inspected and repaired or replaced as appropriate. The reportable quantities for xylene, benzene, toluene, naphthalene, and volatile organic compounds were all exceeded