Home | Search | Emissions | Pollutants | About the Database |
Accident # | No LDEQ Number Available |
State Police # | 05-04110 |
Accident Date | 2005-06-20 |
Report Date | 2005-06-24 |
Follow-up Date | 0000-00-00 |
Follow-up: | No |
Pollutant | Duration | Point Source | Greenhouse Gas | Criteria Pollutant | Ozone forming chemical | Amount of Release |
Flammable Vapor | 19 minutes | FLARE | NO | NO | YES | 551.0 pounds |
Propylene | 19 minutes | FLARE | NO | NO | YES | 367.0 pounds |
Ethylene | 19 minutes | FLARE | NO | NO | YES | 35.0 pounds |
Butene | 19 minutes | FLARE | NO | NO | YES | 2.0 pounds |
Nitrogen Oxide | 19 minutes | FLARE | NO | YES | YES | 1.0 pounds |
Nitrogen Dioxide | 19 minutes | FLARE | NO | YES | YES |
Accident Classified As:
flaring occurred when the wrong fan was shutdown on No35 cooling tower; the breakers were labeled 'A' and 'B' instead of 'East' and 'West' so one was mistakingly shut down
pressure was reduce in No12 depropanizer by temporarily returning the West Cell to service. The flare was relit, which reduced the emissions of propylene and propane to the atmospher
Connect With Us: